FEATURES OF PRODUCTS

・Nox emission 50ppm (O2=0% conversion)
・Achievement of Excellent Economy through High Efficiency
・Achievement of Space Saving by Compactness
・Achievement of Excellent Combustion Performance with abatement of CO emission

SPECIFICATION

TYPE YSG-10 YSG-15 YSG-20 YSG-25 YSG-30
Evaporated Output kg/h 10,000 15,000 20,000 25,000 30,000
Steam Pressure Max. Operating Pressure MPa(G) 0.98・1.57・1.96・2.94
Nor. Operating Pressure MPa(G) 0.69〜2.75
Steam Temperature ℃ Saturate
Boiler Efficiency % 95
Fuel City gas (13A)
Draft method Forced Draft
Burner Type Low NOx Gas Burner
Heating Surface m² 100.0 140.0 180.0 220.5 260.0
Furnace Volume m³ 10.5 16.0 20.0 28.5 32.0
Fuel Consumption Nm³/h 687 1,030 1,373 1,716 2,060
Boiler Height mm(H) 3,300 3,500 3,500 3,800 3,800
Boiler Width mm(W) 3,400 3,700 3,800 4,000 4,000
Boiler Length mm(L) 6,200 7,000 7,800 8,800 9,400
Min. Boiler Installation Area m² 21 26 30 35 38
Net Weight ton 21 25 30 35 40
Weight with Full Water At Normal Water Level m³ 4.7 6 7.1 7.8 8.7
At Full Water m³ 6 7.6 9 10 11.1
Power Consumption kw 37 45 55 10 90
  • 1. Please contact us if you need steam pressure other than above-mentioned.
  • 2. The above-mentioned fuel consumption are calculated based on Normal Working Pressure: 0.69 MPaG, Feed Water Temperature: 20℃.
  • 3. The above size is subject to change more or less as it is approximate.
  • 4. Combustion air rate shall be 1.15.
  • 5. It shall be Economizer-Built-in type
  • 6. Consumption power includes forced draft fan and feed water pump.
  • 7. If you need further requests, please contact us.

CONSTRUCTION

・Combination of Low Nox gas burner, EGR (Exhaust Gas Recirculation) and SI (Steam Injection) has enabled Nox to emit much less.

・Employment of all-welded type combustion chamber and high efficiency heat exchanging tubes has realized a higher performance to raise economy.

・Built-in Economizer has diminished the installation space.
(95% efficiency by built-in economizer has increased to more than 96% by installing outer air heater.)

・We have been exerting a great efforts in order to clear the urban area’s pollution limitations by using the city gas as fuel.

Inquiries about Products